Following several minor errors on the bypass, we asked the manufacturer of the UPS to intervene and check the equipment.
Currently, the UPS seems unable to bypass automatically.
The manufacturer teams and their BE are investigating this problem that seems exceptional.
The situation is currently stable.
Update(s):
Date: 2015-02-13 05:46:03 UTC All bypass module cards eventually have been changed after 2 inadequate attempts.
The UPS is in good working status.
Date: 2015-02-11 11:44:02 UTC Work is complete. Everything went as planned.
Date: 2015-02-11 07:23:23 UTC We have implemented an action plan to take over the load of the UPS on a temporary one on hot swap.
The preparatory work is completed. The operation will begin tonight at 3am.
Date: 2015-02-04 00:05:33 UTC The manufacturer had some issues facing this problem.
We are looking for a fix and preparing in parallel an alternative solution.