FS#6055 — FS#9962 — Main electrical supply

Attached to Project— Datacenters
Maintenance
All of the datacenters
CLOSED
100%
We have a power cut on the main supply to Roubaix 1 and 3.
The generators have taken over.
Date:  Saturday, 04 January 2014, 13:39PM
Reason for closing:  Done
Comment by OVH - Friday, 03 January 2014, 23:02PM

We switched back the GE to the relief cable shortly after the cut-off.
There was no impact on the servers.

One of the 5 GE f this site is faulty.
The manufacturer is there to fix the issue.

We contacted ERDF who will recontact us to return to the "normal" cable.


Comment by OVH - Friday, 03 January 2014, 23:05PM

ERDF will not get back to normal before tomorrow morning.
The meeting was arranged for 9am.

GE, which has not started has been repaired: batteries defected (however they were replaced last year during preventive maintenance ...).
The main GE of Roubaix 1 is again available in N+1 in case of another cut-off tonight.


Comment by OVH - Saturday, 04 January 2014, 13:39PM

ERDF has just performed to the manipulation to get back to normal.
We heard yesterday that the problems come from a mini-tornado that went on towns: Leers / Crois / Wattrelos. Sheet roof flew and hit the 225 kV lines causing failure.

We are on the normal pattern, end of the incident.