FS#7659 — th2-1-6k
Incident Report for Network & Infrastructure
Resolved
A routing card of the router restarted.

We will check.

Update(s):

Date: 2012-11-21 00:52:36 UTC
The router is running properly again.

Date: 2012-11-21 00:49:54 UTC
We fixed the temperature problem.
We have performed works in the rack this afternoon in order to prepare the router upgrade to sup2T which had an impact on the air flow and caused a cooling problem on one of the cards.

Date: 2012-11-21 00:47:16 UTC
We have a temperature problem temperature in the rack. The card has restarted.

Nov 20 19:41:05 GMT: %C6KENV-SP-2-MAJORTEMPALARM: EARL 2/0 inlet temperature crossed threshold #2(=67C). It has exceeded allowed operating temperature range.
Nov 20 19:41:05 GMT: %C6KENV-SP-2-SHUTDOWN_SCHEDULED: shutdown for EARL 2/0 scheduled in 300 seconds

Nov 20 19:49:48 GMT: %C6KPWR-SP-4-DISABLED: power to module in slot 2 set off (temperature out-of-range)
Posted Nov 21, 2012 - 00:46 UTC